GSRM6 Gas-Insulated Ring Main Unit
A sealed SF6 ring main unit that puts load-break, fuse-protection and vacuum-breaker functions in one gas tank — 325 mm per module at 12 kV, so a four-module ring position fits where an air-insulated panel would need three times the floor.



The unit you are reading about
Same tank, same module width: photographed during assembly and after routine test.



Overview
The GSRM6 is a factory-assembled, metal-enclosed ring main unit for 12 kV and 24 kV distribution networks. Switching functions — load break, load break with fuse protection, and vacuum circuit breaking — are housed in a stainless-steel gas tank filled with SF6 at a defined pressure, so live parts are never exposed to ambient humidity, salt fog or dust.
Because the dielectric strength of SF6 is roughly 2.5–3 times that of air at the same pressure, clearances inside the tank collapse and the whole unit becomes modular: a load-switch module is 325 mm wide at 12 kV and 375 mm at 24 kV. A four-module ring position — two cable modules plus two load-switch or breaker modules — occupies 1,345 mm, which is the number to check against your vault drawing.
The design target is distribution duty rather than transmission duty: 630 A continuous, 20 kA for 4 seconds, 50 kA peak. That covers urban ring loops, industrial spurs, wind and solar collector circuits, metro traction substations and any location where a sealed unit removes the need for a ventilated MV room.
Typical installation profile
- Urban distribution loops and double-supply substations
- Underground vaults, basements and metro / light-rail stations
- Coastal plants and high-humidity industrial sites (up to 95% daily average RH)
- High-altitude sites up to 1,500 m at standard filling pressure
- Renewable collector circuits requiring remote switching
Module system
The unit is built from functional modules bolted side by side on a common busbar. You specify the sequence — the same physical platform covers a two-way ring position and an eight-module switching station.
| Code | Function | 12 kV width | 24 kV width |
|---|---|---|---|
| C | Load-switch module | 325 mm | 375 mm |
| D | Cable connection module (no earthing switch) | 325 mm | 375 mm |
| F | Load switch + fuse combination module | 325 mm | 375 mm |
| V | Vacuum circuit-breaker module | 325 mm | 375 mm |
| SL | Busbar sectionalising module (load switch) | 325 mm | 375 mm |
| SVBR | Busbar sectionalising module (vacuum breaker, with busbar lifting) | 650 mm | 650 mm |
| M | Metering module | 695 mm | 695 mm |
| PT | Voltage-transformer module | 370 or 695 mm | 370 or 695 mm |
Total cabinet width = sum of module widths. Example: C + C + C + C at 12 kV = 1,345 mm.
Standard configurations
- 2-module ring position — two load-switch modules for incoming and outgoing cable, no protection.
- 3-module ring position — two load switches plus a fuse-combination module for a 125 A transformer feeder.
- 4-module ring position — two load switches plus a vacuum-breaker module for outgoing feeder protection, plus metering.
- Sectionalising station — SL or SVBR module added to split the busbar between two ring sections.
Voltage variants — which rating serves which system
| System voltage | Rated voltage Um | Power-frequency (phase–earth / open gap) | Lightning impulse (phase–earth / open gap) | Declaration |
|---|---|---|---|---|
| 11 kV | 12 kV | 42 / 48 kV | 75 / 85 kV | IEC 62271-200 |
| 13.8 kV | 12 kV · 15 kV ANSI class | 36 kV (ANSI) / 42 kV (IEC) | 95 kV (ANSI) / 75 kV (IEC) | IEC + ANSI envelope |
| 22 kV | 24 kV | 65 / 79 kV | 125 / 145 kV | IEC 62271-200 |
| 33 kV | 36 kV | 95 kV | 170 kV | C-GIS platform, on request |
One tank design covers 11 kV, 13.8 kV and 22 kV by changing the insulation level and the module width — 325 mm at 12 kV, 375 mm at 24 kV. A 33 kV requirement moves to the GSRM6-36 C-GIS frame, which is quoted against the type-test report your utility or consultant requires.
Rated technical data
| Parameter | Unit | 11 / 13.8 kV (Um 12) | 22 kV (Um 24) |
|---|---|---|---|
| Rated voltage | kV | 12 | 24 |
| Rated frequency | Hz | 50 / 60 | |
| Rated current | A | 630 | 630 |
| Power-frequency withstand, phase-to-earth and between phases | kV | 42 | 65 |
| Power-frequency withstand, across open contacts | kV | 48 | 79 |
| Lightning impulse withstand, phase-to-earth and between phases | kV | 75 | 125 |
| Lightning impulse withstand, across open contacts | kV | 85 | 145 |
| Rated short-time withstand current | kA / s | 20 / 4 | 20 / 4 |
| Rated peak withstand current | kA | 50 | 63 |
| Rated short-circuit making current (peak) | kA | 50 | 63 |
| Rated short-circuit breaking current (V module) | kA | 20 | 25 |
| Rated closed-loop breaking current | A | 630 | 630 |
| Rated cable-charging breaking current | A | 10 | 25 |
| Rated transfer current (F module) | A | 1,700 | 1,400 |
| Mechanical life (load switch / breaker) | operations | 5,000 | 5,000 |
| Gas leak rate | % / year | ≤ 0.1 | |
Values correspond to IEC 62271-1 / 62271-200 minimum requirements for the stated voltage class; final figures follow the type-test report issued for the ordered configuration.
Dimensions and weight envelope
| Modules | Total width A | Base width B | Depth C | Height D |
|---|---|---|---|---|
| 1 module | 370 | 297 | 336 | 370 |
| 2 modules | 695 | 622 | 663 | 695 |
| 3 modules | 1,020 | 947 | 988 | 1,020 |
| 4 modules | 1,345 | 1,272 | 1,313 | 1,345 |
| 5 modules | 1,670 | 1,597 | 1,636 | 1,670 |
Widths scale at a constant 325 mm pitch at 12 kV; 24 kV cabinets use a 375 mm pitch and are quoted per layout.
Operating conditions
| Condition | Value |
|---|---|
| Ambient air temperature | −40 °C … +40 °C |
| Relative humidity, daily average | < 95% |
| Relative humidity, monthly average | < 90% |
| Installation altitude | ≤ 1,500 m at standard filling pressure |
| Seismic intensity | < 9 (Chinese scale) |
| Environment | No fire, explosion, serious contamination, chemical corrosion or severe vibration |
Sites outside these ranges — higher altitude, aggressive chemical atmosphere, ambient above 40 °C — are quotable as special conditions; the gas filling pressure and insulation coordination are recalculated rather than derated on paper.
Standards and tests
- IEC 62271-200 — AC metal-enclosed switchgear and controlgear: ratings, interlocks, IP class, internal arc classification, loss of service continuity category.
- IEC 62271-103 — load-break switches, including closed-loop and cable-charging breaking duties.
- IEC 62271-100 — high-voltage alternating-current circuit breakers for the V module.
- IEC 62271-1 — common specifications: insulation levels, temperature rise, mechanical endurance.
- Routine tests on every unit — power-frequency withstand, insulation resistance, gas leak detection, mechanical operation sequence, wiring and interlock verification.
Configuration options
- Motor-operated mechanisms with FTU / RTU interface for remote control.
- Fault passage indicators, cable fault sensors and temperature/humidity monitoring.
- Current and voltage transformers for metering and protection.
- Earthing switch with position indicator and padlockable operating interface.
- OEM branding, RAL-painted enclosure and customer-specific terminal arrangements.
FAQ
Can the GSRM6 be extended after installation?
Yes. The busbar is designed for side extension, so additional modules bolt onto the existing tank flange. The practical constraint is floor space and cable termination room, not the switchgear itself — which is why we ask for the vault drawing before confirming a layout.
What is the difference between the C, F and V modules?
C is a plain load-break switch for ring in / ring out duty. F adds a fuse holder for transformer protection up to 125 A. V replaces the load switch with a vacuum circuit breaker and protection relay for outgoing feeders that need overcurrent tripping.
How often does the SF6 need topping up?
The tank is sealed for life with a leak rate below 0.1% per year. In practice the annual routine is a pressure-gauge reading against the factory filling record; topping up is an exception, not a maintenance task.
Is a 24 kV unit the same footprint as 12 kV?
No. Insulation clearances grow, so the module pitch increases from 325 mm to 375 mm. A four-module 24 kV unit is roughly 200 mm wider than its 12 kV equivalent — worth checking early if the vault is tight.
What do you need to quote?
System voltage, rated fault level, the single-line diagram or module sequence, quantity, destination port and any automation requirement (FTU / RTU, protocol). Everything else we propose and you confirm.
Need the datasheet for a tender?
We will send the rated-data table, module widths and a dimensioned layout in PDF, plus the type-test reference for your voltage class.
Related voltage classes and build notes
The GSRM6 tank platform is shared across ratings, so a 12 kV layout converts to 24 kV by changing modules rather than the enclosure. Compare the 11 kV, 13.8 kV, 22 kV and 33 kV pages for module widths and withstand levels. For how the tank is welded and tested before dispatch, read how a gas-insulated RMU is built, or see the full switchgear range.