11 kV Gas-Insulated Switchgear
The workhorse of urban loops and industrial parks. 42 kV power-frequency and 75 kV lightning impulse, 630 A continuous, 20 kA / 4 s short-time withstand. 325 mm module width is what makes it fit an existing vault.
Platforms: GSRM6 SF6 RMU · GSG2-12 solid insulated · GSM6-12 unit type · HXGN15-12 air insulated.
Model selection, module width and outgoing feeders are confirmed against your single-line diagram before quotation.
Where the 11 kV class fits
11 kV is the default distribution level in most of Asia, the Middle East and Africa: urban ring loops, industrial parks, airport and port distribution, and the incoming side of a mid-sized plant. A gas-insulated ring main unit is specified at this level because the vault usually already exists — the question is how many modules fit inside it, not how large a room can be poured.
At Um 12 kV the dielectric duty is modest, so the tank stays compact: 325 mm per module against roughly 900 mm for an air-insulated HXGN panel at the same rating. That is why a four-module ring position fits a 1.2 m corridor where four air-insulated panels would not.
11 kV switchgear rated data
| Rated voltage / Um | 12 kV (Um 12) |
|---|---|
| Power-frequency withstand (phase–earth / phase–phase) | 42 kV / 42 kV (48 kV across the open gap) |
| Lightning impulse withstand (1.2/50 µs) | 75 kV (85 kV across the open gap) |
| Rated current | 630 A continuous |
| Short-time withstand | 20 kA for 4 s |
| Peak withstand | 50 kA |
| Breaking capacity (circuit-breaker modules) | 20 kA symmetrical |
| Module width | 325 mm per module; cabinet width grows with module count |
| Enclosure | IP2X inside the substation, IP67 tank, IK07 front |
| Gas loss | ≤ 0.1 % per year, sealed-for-life tank |
| Standards | IEC 62271-200, IEC 62271-100, IEC 62271-103 · IEC 62271-202 where supplied as a kiosk |
What decides fit and price at this class
- Module count before anything else. Two cable modules plus one or two switching modules is the usual ring position; a fourth module is often metering or protection. Count feeders, not functions.
- Fault level. 20 kA / 4 s covers most 11 kV urban loops. Sites fed from a large transformer may need 25 kA — settle it before the drawing is frozen.
- Cable termination side. Left or right entry changes the internal busbar run and therefore the cabinet width on multi-module units.
- Relay and metering. Protection relay, CT/VT and kWh meter can sit in the low-voltage compartment of the same cubicle; specify it at quotation, because retrofitting a compartment later costs more than the relay.
Questions buyers ask about 11 kV gas-insulated switchgear
Can a 12 kV RMU be used on a 13.8 kV system?
No. 13.8 kV needs Um 15 kV insulation — 36 kV power-frequency, 95 kV BIL. The cubicle looks similar, but the insulation and the declared ratings belong to a different product. Order the 13.8 kV variant.
C-GIS or SF6 ring main unit at 11 kV?
An RMU is a C-GIS with a fixed function set: load break, fuse protection, vacuum breaker. If your single-line diagram is a standard two-way ring position, the RMU is cheaper and faster. If you need busbar-section switching or a different sequence, specify a modular C-GIS.
How many modules fit a 1.2 m vault?
Four at 325 mm per module, plus cable clearance. Send the vault dimensions with the single-line diagram and the layout comes back with the drawing, not as a catalogue number.
Do you supply type-test reports?
On request with the quotation. Routine test records — power-frequency withstand, partial discharge, gas leak, mechanical operation — travel with each serial number.
What is the lead time?
Standard configurations are quoted within 24 hours of receiving the single-line diagram; production scheduling is confirmed with the purchase order.