11 kV system · Um 12 kV

11 kV Gas-Insulated Switchgear

The workhorse of urban loops and industrial parks. 42 kV power-frequency and 75 kV lightning impulse, 630 A continuous, 20 kA / 4 s short-time withstand. 325 mm module width is what makes it fit an existing vault.

Um 12 kV42 / 75 kV630 A20 kA / 4 s

Platforms: GSRM6 SF6 RMU · GSG2-12 solid insulated · GSM6-12 unit type · HXGN15-12 air insulated.

Model selection, module width and outgoing feeders are confirmed against your single-line diagram before quotation.

Where the 11 kV class fits

11 kV is the default distribution level in most of Asia, the Middle East and Africa: urban ring loops, industrial parks, airport and port distribution, and the incoming side of a mid-sized plant. A gas-insulated ring main unit is specified at this level because the vault usually already exists — the question is how many modules fit inside it, not how large a room can be poured.

At Um 12 kV the dielectric duty is modest, so the tank stays compact: 325 mm per module against roughly 900 mm for an air-insulated HXGN panel at the same rating. That is why a four-module ring position fits a 1.2 m corridor where four air-insulated panels would not.

11 kV switchgear rated data

Rated voltage / Um12 kV (Um 12)
Power-frequency withstand (phase–earth / phase–phase)42 kV / 42 kV (48 kV across the open gap)
Lightning impulse withstand (1.2/50 µs)75 kV (85 kV across the open gap)
Rated current630 A continuous
Short-time withstand20 kA for 4 s
Peak withstand50 kA
Breaking capacity (circuit-breaker modules)20 kA symmetrical
Module width325 mm per module; cabinet width grows with module count
EnclosureIP2X inside the substation, IP67 tank, IK07 front
Gas loss≤ 0.1 % per year, sealed-for-life tank
StandardsIEC 62271-200, IEC 62271-100, IEC 62271-103 · IEC 62271-202 where supplied as a kiosk

What decides fit and price at this class

  • Module count before anything else. Two cable modules plus one or two switching modules is the usual ring position; a fourth module is often metering or protection. Count feeders, not functions.
  • Fault level. 20 kA / 4 s covers most 11 kV urban loops. Sites fed from a large transformer may need 25 kA — settle it before the drawing is frozen.
  • Cable termination side. Left or right entry changes the internal busbar run and therefore the cabinet width on multi-module units.
  • Relay and metering. Protection relay, CT/VT and kWh meter can sit in the low-voltage compartment of the same cubicle; specify it at quotation, because retrofitting a compartment later costs more than the relay.

Questions buyers ask about 11 kV gas-insulated switchgear

Can a 12 kV RMU be used on a 13.8 kV system?

No. 13.8 kV needs Um 15 kV insulation — 36 kV power-frequency, 95 kV BIL. The cubicle looks similar, but the insulation and the declared ratings belong to a different product. Order the 13.8 kV variant.

C-GIS or SF6 ring main unit at 11 kV?

An RMU is a C-GIS with a fixed function set: load break, fuse protection, vacuum breaker. If your single-line diagram is a standard two-way ring position, the RMU is cheaper and faster. If you need busbar-section switching or a different sequence, specify a modular C-GIS.

How many modules fit a 1.2 m vault?

Four at 325 mm per module, plus cable clearance. Send the vault dimensions with the single-line diagram and the layout comes back with the drawing, not as a catalogue number.

Do you supply type-test reports?

On request with the quotation. Routine test records — power-frequency withstand, partial discharge, gas leak, mechanical operation — travel with each serial number.

What is the lead time?

Standard configurations are quoted within 24 hours of receiving the single-line diagram; production scheduling is confirmed with the purchase order.